HTAF Series Active Power FilterHTAF Series Active Power Filter
description:
Operation principle
HTAF active power filter is mainly consisted of instruction current arithmetic circuit and compensation current generating circuit. Instruction current arithmetic circuit monitors current in line on real time, changes analog current signal into digital signal, deals signal in DSP, divides harmonic and fundamental wave, sends drive pulse to impregnated current generating circuit in PWM form, drives IGBT or IPM power module, produces current with opposite polarity and same amplitude of compensating current and sends current into electrified wire netting, compensates or counteracts harmonic current and cancels electric harmonic actively. In this way, harmonic current is dealt actively, quickly and completely.
HTAF active power filter can supply required fundamental reactive compensating current, achieves dynamic reactive compensation and improves power factor of electrified wire netting.
 
HTAF operating principle block diagram
 
 
HTAF filter principle schematic
 
Main disadvantages of harmonic
Increasing electrical equipment’s loads, reducing system power factor, reducing valid capacity and efficiency of electric generator and electric power transmission and electrical equipment, wasting lines and equipment, losing electric energy
Overload resonance vibration of reactive compensation capacitor, compensating equipment burnout or not work because of over current and over voltage
Mechanical vibration produced by pulsating torque which affect the quality of produce and service time of electrical motor
eddy current and Kelvin effect make electrical motor, transformer and transfer line add power loss and overheat, waste electrical energy and accelerate insulation degradation
harmonic voltage increases electric-field intensity of insulating medium by direct proportion of peak voltage, reducing equipment service time
Harmonic current of the multiple of three cause neutral line becoming overload in three phase four lines system and produces circuit current in transformer coils of delta connection. Coil current is beyond rating value and accident will happen in serious situation.
Harmonic can change acting characteristic of protective relay, cause relay protective action’s maloperation and regional power off.
Harmonic can change voltage and current’s change rate and peak value, delay arc extinguished, affect breaking capacity of circuit breaker.
metering equipment make metering deviation especial induction electric energy meter
Interfering neighboring electric power, electrical equipment and communication system, system working abnormally
 
HTAF Series Active Power Filter Characteristic
1.        Parallel access, install and maintain easily
2.        Filter 2nd to 50th harmonic wave
3.        Filter more than 95% harmonic wave
4.        Filter wave automatically, never affected by impedance in electrified wire netting
5.        Dynamic real-time track-compensation, quick response
6.        Filter effect is not affected by electrified wire netting resistance
7.        Inhibit overload automatically, no resonance danger
8.        No upper frequency ripples current interference
9.        Multi-module parallel operation
10.    Compensate harmonic and reactive power simultaneously
11.    High efficient filter, low electric energy loss 
12.    Multi-protection to ensure system operate safely and reliably
13.    Digital control, Chinese language LCD
14.    Fault self-diagnostic function, history recording function
15.    RS485 interface, standard MODBUS communication agreement
 
Main technology parameter
item
index
 
Rating compensating current of single machine
400V/50A-200A, 690V/30A-120A
Rating compensating capacity of single machine
33kVar — 133 kVar
mains voltage
three phase 380V/690V±15%
mains frequency
50/60 Hz±2%
Filter harmonic frequency
2~50th
Filter frequency
≥95%
Response time
≤20 ms
Power loss
≤3% rating compensation capacity
Noise
≤65 dB
Protection function
Abnormal voltage protection; over load limitation; system error protection; system overheat protection
External dimension mm
800×1000×2200 standard GGD machine cabinet
Storage Temperature
-40~55 ℃
Serving temperature
-10~40 ℃
Relative humidity
≤95%, not condensation
altitude
≤2000m,Reduce rating capacity in higher altitude
 

 